Troubleshoot with the Indicators
Indication
Probable Cause
System Power
Off
Not active; field power is off or dc-dc converter problem
Green
System power on; dc-dc converter active (5V)
Field Power
Off
Not active; field power is off
Green
Power on; 24V present
Module Status
Off
No power applied to device
Flashing Red/Green
LED powerup test (module self-test)
Green
Device is operating normally
Flashing Red
Recoverable fault has occurred:
• Firmware (NVS) update
• Network IP Address changed
• CPU load exceeded
Solid Red
Unrecoverable fault has occurred:
• Self-test failure (checksum failure, or ramtest failure at
powerup)
• Firmware fatal error
System Power
Field Power
43248aent
Module Status
Network Activity
Network Status