Troubleshoot with the indicators, 12 point i/o ethernet/ip adapter publication – Rockwell Automation 1734-AENT Point I/O Ethernet Adapter Installation Instructions User Manual

Page 12

Advertising
background image

12 POINT I/O EtherNet/IP Adapter

Publication

1734-IN590B-EN-P - February 2005

Troubleshoot with the Indicators

Indication

Probable Cause

System Power

Off

Not active; field power is off or dc-dc converter problem

Green

System power on; dc-dc converter active (5V)

Field Power

Off

Not active; field power is off

Green

Power on; 24V present

Module Status

Off

No power applied to device

Flashing Red/Green

LED powerup test (module self-test)

Green

Device is operating normally

Flashing Red

Recoverable fault has occurred:

• Firmware (NVS) update

• Network IP Address changed

• CPU load exceeded

Solid Red

Unrecoverable fault has occurred:

• Self-test failure (checksum failure, or ramtest failure at

powerup)

• Firmware fatal error