Rockwell Automation 1734-AENT Point I/O Ethernet Adapter Installation Instructions User Manual
Page 13

POINT I/O EtherNet/IP Adapter 13
Publication
1734-IN590B-EN-P - February 2005
Indication
Probable Cause
Network Status
Off
Device not initialized. The module does not have an IP address.
Flashing Green
No CIP connections. Device has an IP address, but no CIP
connections are established.
Green
CIP connections. Device on-line and has an IP address, and CIP
connections are established.
Flashing Red
One or more EtherNet connections has timed-out.
Red
No link. The module is not physically connected to a powered
EtherNet Device.
Flashing Red/Green
The module is performing a self-test (only occurs during
powerup test).
Network Activity
Off
No link established.
Flashing Green/Off
Transmit or receive activity.
Steady Green
Link established.
PointBus Status
Off
Device not powered - check module status indicator.
Flashing Red/Green
LED powerup test.
Flashing Red
Recoverable fault has occurred:
• at powerup the number of expected modules
does not equal the number of modules present
• a module is missing
• node fault (I/O connection timeout)