Specifications – Rockwell Automation 1734-AENT Point I/O Ethernet Adapter Installation Instructions User Manual

Page 16

Advertising
background image

16 POINT I/O EtherNet/IP Adapter

Publication

1734-IN590B-EN-P - February 2005

Specifications

Adapter Specifications

Expansion I/O Capacity Maximum of 63 modules

Maximum of 5 Rack Optimized connections (for digital modules
only)
Maximum of 20 direct connections
1734-AENT backplane current output = 1.0A.
The actual number of modules can vary. Add up the current
requirements of the modules you want to use to make sure they do
not exceed the amperage limit of 1.0A for the 1734-AENT.
Backplane current can be extended beyond 1.0A by using
1734-EP24DC backplane extension Power Supplies. Add multiple
1734-EP24DC modules to reach the 63 module maximum).
Cat. No.

PointBus Current Requirements

1734-IB2

75mA

1734-IB4

75mA

1734-IB8

75mA

1734-IV2

75mA

1734-IV4

75mA

1734-OB2

75mA

1734-OB4

75mA

1734-OB8

75mA

1734-OB2E

75mA

1734-OB2EP

75mA

1734-OB4E

75mA

1734-OB8E

75mA

1734-OV2E

75mA

1734-OV4E

75mA

1734-OW2

80mA

1734-OX2

100mA

1734-IE2C

75mA

1734-OE2C

75mA

1734-IE2V

75mA

1734-OE2V

75mA

1734-IA2

75mA

1734-IM2

75mA

1734-OA2

75mA

1734-IJ2

160mA

1734-IK2

160mA

1734-IR2

220mA

1734-IT2I

175mA

1734-SSI

110mA

1734-VHSC5

180mA

1734-VHSC24

180mA

1734-232ASC

75mA

1734-485ASC

75mA

EtherNet
Communication Rate

10/100Mbits/s, half or full-duplex

Advertising