Specifications – Rockwell Automation 1771-OP Protected AC (120V) Output Module Installation Instructions User Manual

Page 11

Advertising
background image

Protected AC Output Module

11

Publication 1771-IN077A-EN-P - October 2002

Outputs per Module

8

Module Location

1771 I/O chassis

Output Voltage Range

92 to 138V ac @ 47 - 63Hz

Output Current Rating

1.5A per output - not to exceed 6A per module

Surge Current (maximum)

4A per output for 8.3ms at 120V ac, repeatable every 1s

Minimum Load Current

50mA per output @ 120V ac, 60Hz

On State Voltage Drop

2V at 100mA

Off State Leakage Current (max.)

5mA per output @ 120V ac

Power Dissipation

10.7 Watts (max.), 1.1 Watts (min.)

Thermal Dissipation

36.6 BTU/hr (max.), 3.4 BTU/hr (min.)

Adjacent Slot Power Dissipation

10 Watts maximum

Backplane Current

210mA @ 5V dc 5%

Opto-electrical Isolation

Tested to 1500V ac rms for 1s

Environmental Conditions

Operational Temperature

IEC 60068-2-1 (Test Ad, Operating Cold)

IEC 60068-2-2 (Test Bd, Operating Dry Heat)

IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

32 to 140°F (0 to 60°C)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)

IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)

IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock)

-40 to 185°F (-40 to 85°C)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)

5 to 95% noncondensing

Shock

Operating

Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30g

50g

Vibration

IEC 60068-2-6 (Test Fc, Operating)

2g @ 10-500Hz

Enclosure Type Rating

None (open style)

Keying

Between 6 and 8

Between 26 and 28

Fuses

5A, 250V Bussman MTH5, IEC 127 Type F

Field Wiring Arm

Cat. No. 1771-WA

Field Wiring Arm ScrewTorque

7-9 pound-inches (0.7-1.0Nm)

Conductors

Wire Size

Category

14-22AWG (2.5-0.25mm

2

) stranded copper wire rated at 75

o

C or

greater

1

3/64 inch (1.2mm) insulation (max)

1

2

Certifications

(when product is marked)

UL

UL Listed Industrial Control Equipment

CSA

CSA Certified Process Control Equipment

1 One or two 14-22 AWG solid or stranded copper wires per terminal. Must be same size. Do not intermix solid and stranded wires.

Use copper wire only.

2 Use this conductor category information for planning conductor routing . Refer to publication 1770Ć4.1, Industrial Automation Wiring and

Grounding Guidelines."

Specifications