Rockwell Automation 1771-OP Protected AC (120V) Output Module Installation Instructions User Manual

Page 5

Advertising
background image

Protected AC Output Module

5

Publication 1771-IN077A-EN-P - October 2002

!

ATTENTION

Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic
discharge, which can cause internal damage and
affect normal operation. Follow these guidelines
when you handle this equipment:

Touch a grounded object to discharge potential
static.

Wear an approved grounding wriststrap.

Do not touch connectors or pins on component
boards.

Do not touch circuit components inside the
equipment.

If available, use a static–safe workstation.

When not in use, keep modules in appropriate
static–safe packaging.

Key the Backplane Connector

Place your module in any slot in the chassis
except the leftmost slot which is reserved for
processors or adapters.

Observe the following precautions
when inserting or removing keys:

insert or remove keys with your
fingers

make sure that key placement is
correct

Incorrect keying or the use of a tool
can result in damage to the
backplane connector and possible
system faults.

ATTENTION

!

Position the keying bands in the backplane connectors to correspond to

the key slots on the module.

Place the keying bands:

- between 6 and 8

- between 26 and 28

You can change the position of these bands if

subsequent system design and rewiring makes

insertion of a different type of module necessary.

Upper

Connector

11022ĆI

I/O chassis