Rockwell Automation 1771-OP Protected AC (120V) Output Module Installation Instructions User Manual

Page 7

Advertising
background image

Protected AC Output Module

7

Publication 1771-IN077A-EN-P - October 2002

1. Make certain all power is removed from the module before

making wiring connections.

2. Swing the wiring arm up into position on the front of the module.

The locking tab on the module will secure it into place.

3. Make your connections to the field wiring arm as shown in

Figure 1. (Use the label on the front of the wiring arm to identify
your wiring.)

IMPORTANT

The field wiring arm terminal identification
number is not the same as the number of the bit
which controls that output.

You should identify the labels on the wiring arm with the name or
number of the device connected at each terminal.

Figure 1

Connection Diagram for the 1771ĆOP Protected Output Module

A

O

1

2

3

4

5

6

7

B

L2

L2

ac Low

L1

120V ac High

ac Device

controlled by termiĆ

nal

L1

(Actual wiring runs in this direction.)

11884-I

Output 03

Output 02

Output 01

Output 00

Not used

Not used

Not used

Not used

Connect the high side of incoming power to the L1 terminal, and the
low side to the L2 terminal.

ATTENTION

!

Paralleling outputs may result in damage to the
module.