ATTENTION
!
Remove power from the 1771 I/O chassis
backplane and wiring arm before removing or
installing an I/O module.
•
Failure to remove power from the backplane or
wiring arm could cause module damage,
degradation of performance, or injury.
•
Failure to remove power from the backplane
could cause injury or equipment damage due to
possible unexpected operation.
Swing the chassis locking bar down into place to secure
the modules. Make sure the locking pins engage.
1771ĆA1B, ĆA2B, ĆA3B, ĆA3B1, ĆA4B I/O chassis
1771ĆA1B, ĆA2B, ĆA3B1, ĆA4B Series B I/O chassis
locking tab
card guides
Module
Module
19809
card guides
locking bar
locking bar pin
Snap the chassis latch over
the top of the module to secure it.
1
17643
wiring arm
install
remove
horizontal bar
Attach the wiring arm (1771ĆWA) to the horizontal
bar at the bottom of the I/O chassis.
The wiring arm pivots upward and connects with
the module so you can install or remove the
module without disconnecting the wires.
1771ĆWA
2
You make connections to the module through the 1771-WA field
wiring arm shipped with the module. The arm pivots on the chassis
to connect with the 8 terminals on the front of the module. The
wiring arm allows the module to be removed from the chassis
without disconnecting wiring.
Install the Module and Field
Wiring Arm
Connect Wiring to the