Specifications – Rockwell Automation 1756-ENET/B ControlLogix EtherNet Comm. Interface Module, Series B Installation Instructions User Manual

Page 16

Advertising
background image

16 ControlLogix Ethernet Communication Interface Module

Publication

1756-IN053D-EN-P - June 2002

Specifications

Module Location

Any slot in the ControlLogix chassis

Maximum Backplane
Current Load

900mA @ 5.1V dc
350mA @ 24V dc from I/O chassis backplane

Power Dissipation

13.3W maximum

Operating
Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0 to 60°C (32 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):

–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):

5 to 95% non-condensing

Shock

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

Operating 30g
Non-operating 50g

Vibration

IEC 60068-2-6 (Test Fc, Operating):

5g @ 10-500Hz

Emissions

CISPR 11:

Group 1, Class A

ESD Immunity

IEC 61000-4-2:

6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1kHz sine-wave 80%AM from 30MHz to
1000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

EFT/B Immunity

IEC 61000-4-4:

±2kV at 5kHz on communications ports

Surge Transient
Immunity

IEC 61000-4-5:

+2kV line-earth (CM) on shielded ports

Conducted RF
Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz

Advertising