Troubleshooting – Rockwell Automation 1791D-N4CV2X CompactBlock I/O for DeviceNet Expansion Module I.I. User Manual

Page 12

Advertising
background image

12 CompactBlock I/O Analog Combination Input/Output Expansion Module

Publication

1791D-IN002A-EN-P - June 2003

The DeviceNet Network uses advanced network technology,
producer/consumer communication, to increase network functionality and
throughput. Visit our web site at

http://www.ab.com/networks for producer/consumer technology
information and updates.

Troubleshooting

Refer to the following LED indicators to troubleshoot the module.

Expansion Status Indicator

LED Indicator: Status:

Solid Green/On

• Passed internal diagnostics
• Communication over bus
• Analog converter and MPU operating properly

Flashing Red

Recoverable fault (no communication)

Solid Red

Unrecoverable fault (Hardware error)

Off

None of the above conditions is true

Expansion Power Indicator

LED Indicator: Status:

Solid Green

Module powered

Off

Module not powered

Input Channel Status Indicator

LED Indicator: Status:

Solid Green/On Input channel operating properly

Flashing Red

Input channel overrange or open wire @ 4-20mA current mode

Off

Neither of the above conditions is true