Rockwell Automation 1791D-N4CV2X CompactBlock I/O for DeviceNet Expansion Module I.I. User Manual

Page 15

Advertising
background image

CompactBlock I/O Analog Combination Input/Output Expansion Module 15

Publication

1791D-IN002A-EN-P - June 2003

Output Specifications (continued)

Robustness

• Voltage output overload, including short

circuit without damage

• Current output overload, including open

circuit without damage

General Specifications

Indicators

Exp. status - green/red
Exp Powered status - green
Input status - green/red
Output status - green/red

Isolation

500V ac/60s

Auxiliary Power

Voltage

Current

21.6 -26.4V dc
100mA

Expansion Power
Voltage
Current

5V dc

100mA

Expansion Module Dimensions

115mm X 50mm X 38mm
4.4in X 1.97in X 1.5in

Field Wiring Tightening Torque

5-7lb-in. (0.5-0.6 Nm)

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0 to 60°C (32 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating
Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating
Dry Heat),

IEC 60068-2-14 (Test Na, Un-packaged
Non-operating Thermal Shock):

-40 to 85°C (-40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating

Damp Heat):

5-95% non-condensing