10 SLC 5/03, SLC 5/04, and SLC 5/05 Modular Processors

Publication 1747-IN009B-EN-P - March 2008

2. Set the communication parameters of the software to match the default

parameters of the processor.

Replace the Battery

Your SLC processor provides back-up power for RAM through a replaceable lithium
battery. This battery provides back-up for approximately 2 years. The BATT LED
indicator on the front of the processor alerts you when the battery voltage has
fallen below a threshold level.

To replace the lithium battery follow these steps.

1. Remove power from the SLC 500 power supply.

2. Remove the processor from the chassis by pressing the retainer clips at both

the top and bottom of the module and slide it out.

Channel 0 Configuration Channel 1 Configuration

SLC 5/03, 5/04, 5/05

SLC 5/03

SLC 5/04

SLC 5/05

DF1 Full-duplex:

no handshaking

19.2 Kbaud

CRC Error Check

duplicate detect on

no parity

DH-485:

19.2 Kbaud

node address = 1

DH+:

57.6 Kbaud

node address = 1

Ethernet:

BOOTP enabled

ATTENTION

Do not remove the processor from the SLC 500 chassis until all power is
removed from the SLC 500 power supply. If you remove the power supply while
power is applied, an electrical arc can occur. This could cause an explosion in
hazardous location installations.

ATTENTION

Do not expose the processor to surfaces or other areas that may typically hold
an electrostatic charge. Electrostatic charges can alter or destroy memory.

Advertising