Loading your software, Establish communication to the processor, Refer to your programming software documentation – Rockwell Automation 1747-L5xx SLC 5/03, 5/04, and 5/05 Modular Processors User Manual

Page 9

Advertising
background image

SLC 5/03, SLC 5/04, and SLC 5/05 Modular Processors 9

Publication 1747-IN009B-EN-P - March 2008

Loading Your Software

Refer to your programming software documentation.

Establish Communication to the Processor

1. Refer to the following table to establish communication between the

processor and your personal computer.

Processor

Procedure

SLC 5/03

Connect the 1747-PIC interface from the processor to your personal computer serial port
or connect the 1747-UIC interface from the processor to your personal computer USB
port to the processor using the 1747-C13 or 1747-CP3 cable. You can also use a
1784-PKTX(D) or 1784-PCMK interface, or a 1747-CP3 cable from channel 0 of the
processor to the personal computer serial port.

SLC 5/04

Connect a 1747-CP3 cable from channel 0 of the processor to the personal computer
serial port or connect the 1747-UIC interface from channel 0 of the processor to your
personal computer USB port, or use a 1784-PKTX(D) or 1784-PCMK interface.

SLC 5/05

Connect a 1747-CP3 cable from channel 0 of the processor to the personal computer
serial port, or connect the 1747-UIC interface converter from channel 0 of the processor
to your personal computer USB port. For Ethernet connection, connect channel 1 of the
processor and the PC Ethernet Card to an Ethernet hub using 10/100Base-T compatible

cable.

(1)

(1)

EtherNet/IP address must first be set via BOOTP or an RS-232 connection.

POWER

RUN

FLT

BATT

FORCE

DH485

RS232

POWER

RUN

FLT

BATT

FORCE

DH+

RS232

POWER

RUN

FLT

BATT

FORCE

ENET

RS232

Power Supply and LED Indicators

Indicates the LED indicator is OFF.

Indicates the LED indicator is ON.

Indicates the LED indicator is FLASHING.

Status of LED indicator does not matter.

SLC 5/05

SLC 5/04

SLC 5/03