Communication

Communication options for the SLC 5/03, 5/04, and 5/05 processors are as follows:

DH485

RS-232 protocols (DF1 Full-duplex, DF1 Half-duplex master/slave, DF1
Radio Modem, DH-485, or ASCII)

Data Highway Plus (A ControlLogix Gateway is required for the SLC 5/03
and SLC 5/05 processors.)

Ethernet TCP/IP (A 1761-NET-ENI interface module is required for the SLC
5/03 and SLC 5/04 processors)

ControlNet (via a 1747-KFC15 module)

DeviceNet (via a 1761-NET-DNI interface module)

Specifications

Attribute

Value

Power supply loading at 5V dc

500 mA for the SLC 5/03 processor

1.0 A for the SLC 5/04 and 5/05 processors

Power supply loading at 24V dc

175 mA for the SLC 5/03 processor

0 mA for the SLC 5/04 processor

(1)

(1)

SLC 5/04 Processors manufactured prior to April 2002 draw 200 mA at 24V dc. Check your label to verify your processor’s
current draw.

0 mA for the SLC 5/05 processor

Program scan hold-up time after loss of
power

20 ms...3 s (dependent on power supply loading)

Noise immunity

NEMA Standard ICS 2-230

Vibration

Displacement: 0.015 in., peak-to-peak at 5-57 Hz

Acceleration: 2.5 g at 57...2000 Hz

Shock, operating

30 g

Ambient temperature rating, operating

0...60 °C (32...140 °F)

Ambient temperature rating, storage

-40...85 °C (-40...185 °F)

Humidity

5 to 95% without condensation

Agency certification
See http://ab.com for declarations of
conformity, certificates, and other
certification details.

UL Listed Industrial Control Equipment
C-UL Listed Industrial Control Equipment for use in
Canada
UL Listed Industrial Control Equipment for use in
Class I, Division 2, Hazardous Locations Groups A, B,
C or D
CE compliant for all applicable directives
C-Tick marked for all applicable acts