Input specifications – Rockwell Automation 1762-IQ8 MicroLogix DC Input Module User Manual

Page 12

Advertising
background image

12

MicroLogix™ 1762-IQ8 DC Input Module

1762-IN004A-US-P

Input Specifications

Specification

1762-IQ8

Voltage Category

24V dc (sink/source)

(1)

(1)

Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the
field device. Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are
driven by a current sourcing field device. Field devices connected to the negative side (DC Common) of
the field power supply are sinking field devices. Field devices connected to the positive side (+V) of the
field supply are sourcing field devices.

Operating Voltage Range

10 to 30V dc at 30°C (86°F)
10 to 26.4V dc at 55°C (131°F)

Number of Inputs

8

Bus Current Draw (max.)

50 mA at 5V dc (0.25W)

Heat Dissipation (max.)

3.7 Total Watts

Signal Delay (max.)

On Delay: 8.0 ms
Off Delay: 8.0 ms

Off-State Voltage (max.)

5V dc

Off-State Current (max.)

1.5 mA

On-State Voltage (min.)

10V dc

On-State Current

2.0 mA min. at 10V dc
8.0 mA nominal at 24V dc
12.0 mA max. at 30V dc

Inrush Current (max.)

250 mA

Nominal Impedance

3K

Ω

IEC Input Compatibility

Type 1+

Power Supply Distance Rating

6

Isolated Groups

Group 1: inputs 0 to 7 (internally connected commons)

Input Group to Backplane
Isolation

Verified by one of the following dielectric tests: 1200V ac for 1
sec. or 1697V dc for 1 sec.
75V dc working voltage (IEC Class 2 reinforced insulation)

Vendor I.D. Code

1

Product Type Code

7

Product Code

96