Din rail mounting, Panel mounting – Rockwell Automation 1762-IQ8 MicroLogix DC Input Module User Manual

Page 6

Advertising
background image

6

MicroLogix™ 1762-IQ8 DC Input Module

1762-IN004A-US-P

DIN Rail Mounting

The module can be mounted using the following DIN rails: 35 x 7.5 mm
(EN 50 022 - 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).

Before mounting the module on a DIN rail, close the DIN rail latch. Press the
DIN rail mounting area of the module against the DIN rail. The latch will
momentarily open and lock into place.

Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or
1492-EAH35) for vibration or shock environments.

Panel Mounting

Use the dimensional template shown below to mount the module. The preferred
mounting method is to use two M4 or #8 panhead screws per module. M3.5 or #6
panhead screws may also be used, but a washer may be needed to ensure a good
ground contact. Mounting screws are required on every module.

Note:

For environments with greater vibration and shock concerns, use the
panel mounting method described below, instead of DIN rail
mounting.

End Anchor

End Anchor

MicroLogix 1200 MicroLogix 1200

ControllerController

MicroLogix 1200 MicroLogix 1200

Expansion I/OExpansion I/O

MicroLogix 1200 MicroLogix 1200

Expansion I/OExpansion I/O

MicroLogix 1200 MicroLogix 1200

Expansion I/OExpansion I/O

90
(3.54)

100
(3.94)

40.4
(1.59)

40.4
(1.59)

14.5
(0.57)

For more than 2 modules: (number of modules - 1) x 40 mm (1.58 in.)

NOTE: All dimensions
are in mm (inches).
Hole spacing
tolerance: ±0.4 mm
(0.016 in.).