MicroLogix™ 1762-IQ8 DC Input Module
5
1762-IN004A-US-P
Mounting
Minimum Spacing
Maintain spacing from 
enclosure walls, 
wireways, adjacent 
equipment, etc. Allow 
50.8 mm (2 in.) of space 
on all sides for adequate 
ventilation, as shown:
!
ATTENTION: Do not remove protective debris strip until after 
the module and all other equipment near the module is mounted and 
wiring is complete. Once wiring is complete and the module is free 
of debris, carefully remove protective debris strip. Failure to 
remove strip before operating can cause overheating.
Note:
1762 expansion I/O may be mounted horizontally only.
!
ATTENTION: During panel or DIN rail mounting of all devices, 
be sure that all debris (metal chips, wire strands, etc.) is kept from 
falling into the module. Debris that falls into the module could 
cause damage when power is applied to the module.
MicroLogix
1200
1762 I/O
1762 I/O
1762 I/O
Side
Side
Top
Bottom