Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or 
non-hazardous locations only. The following ATTENTION statement applies to 
use in hazardous locations.
!
ATTENTION: EXPLOSION HAZARD
•
Substitution of components may impair suitability for Class I, 
Division 2.
•
Do not replace components or disconnect equipment unless 
power has been switched off.
•
Do not connect or disconnect components unless power has 
been switched off.
•
This product must be installed in an enclosure.
•
In Class I, Division 2 applications, the bus connector must be 
fully seated and the bus connector cover must be snapped in 
place.
•
In Class I, Division 2 applications, all modules must be 
mounted in direct contact with each other as shown on page 6. 
If DIN rail mounting is used, an end stop must be installed 
ahead of the controller and after the last 1762 I/O module.