Input wiring – Rockwell Automation 1762-IQ8 MicroLogix DC Input Module User Manual

Page 8

Advertising
background image

8

MicroLogix™ 1762-IQ8 DC Input Module

1762-IN004A-US-P

Input Wiring

Basic wiring

(1)

of input devices to the 1762-IQ8 is shown below.

A write-on label is provided with the module. Mark the identification of each
terminal with permanent ink, and slide the label back into the door.

(1)

Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between the I/O module and the
field device. Sourcing I/O circuits supply (source) current to sinking field devices. Sinking I/O circuits are
driven by a current sourcing field device. Field devices connected to the negative side (DC Common) of
the field power supply are sinking field devices. Field devices connected to the positive side (+V) of the
field supply are sourcing field devices.

!

ATTENTION: Be careful when stripping wires. Wire fragments
that fall into a module could cause damage when power is applied.
Once wiring is complete, ensure the module is free of all metal
fragments.

!

ATTENTION: Miswiring of the module to an AC power source
will damage the module.

IN 7

IN 5

IN 3

IN 1

DC

COM

IN 6

IN 4

IN 2

IN 0

24V dc

DC

COM

Commons are
connected internally.

+DC (sinking)
-DC (sourcing)

-DC (sinking)
+DC (sourcing)

Advertising