Communicate with your module – Rockwell Automation 1734-OE2V/C Point I/O 2-Current and 2-Voltage Output Analog Modules User Manual

Page 11

Advertising
background image

POINT I/O 2 Current Output and 2 Voltage Output Analog Modules 11

Publication

1734-IN002C-EN-E - April 2005

Communicate with Your Module

POINT I/O modules send (consume) and receive (produce) I/O
messages. You map these messages into the processor’s memory.

These modules produce 2 bytes of input data (scanner Rx) (fault
status). These modules consume 4 bytes of output data (scanner Tx).

Message size: 2 Bytes

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Produces
(scanner Rx)

High Byte - Channel 1 Status

Low Byte - Channel 0 Status

Not used

H
C
A

L
C
A

C
M

C
F

Not used

H
C
A

L
C
A

C
M

C
F

Where:

CF = Channel Fault status; 0 = no error, 1 = fault
CM = Calibration Mode; 0 = normal, 1 = calibration mode
HCA = High Clamp Alarm; 0 = no error, 1 = fault
LCA = Low Clamp Alarm; 0 = no error, 1 = fault

Message size: 4 bytes

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Consumes
(scanner Tx)

Output Channel 0 High Byte

Output Channel 0 Low Byte

Output Channel 1 High Byte

Output Channel 1 Low Byte