Communicate with your module – Rockwell Automation 1734-OE2V/C Point I/O 2-Current and 2-Voltage Output Analog Modules User Manual
Page 11
![background image](/manuals/579554/11/background.png)
POINT I/O 2 Current Output and 2 Voltage Output Analog Modules 11
Publication
1734-IN002C-EN-E - April 2005
Communicate with Your Module
POINT I/O modules send (consume) and receive (produce) I/O
messages. You map these messages into the processor’s memory.
These modules produce 2 bytes of input data (scanner Rx) (fault
status). These modules consume 4 bytes of output data (scanner Tx).
Message size: 2 Bytes
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Produces
(scanner Rx)
High Byte - Channel 1 Status
Low Byte - Channel 0 Status
Not used
H
C
A
L
C
A
C
M
C
F
Not used
H
C
A
L
C
A
C
M
C
F
Where:
CF = Channel Fault status; 0 = no error, 1 = fault
CM = Calibration Mode; 0 = normal, 1 = calibration mode
HCA = High Clamp Alarm; 0 = no error, 1 = fault
LCA = Low Clamp Alarm; 0 = no error, 1 = fault
Message size: 4 bytes
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Consumes
(scanner Tx)
Output Channel 0 High Byte
Output Channel 0 Low Byte
Output Channel 1 High Byte
Output Channel 1 Low Byte