General Specifications
(Continued)

1734-OE2C

1734-OE2V

Radiated RF Immunity

IEC 61000-4-3:
10 V/m with 1kHz sine-wave 80%AM from 30 MHz to
2000 MHz
10 V/m with 200 Hz 50% Pulse 100%AM at 900 Mhz
10 V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz

EFT/B Immunity

IEC 61000-4-4:
±3 kV at 2.5 kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:
±2 kV line-earth(CM) on shielded ports

Conducted RF Immunity

IEC61000-4-6
10 Vrms with 1 kHz sine-wave 80%AM
from 150 kHz to 80 MHz

Enclosure Type Rating

None (open-style)

Wire Size

14 AWG (2.5mm

2

) - 22 AWG (0.25mm

2

) solid or stranded

copper wire rated at 75

o

C or greater

3/64 inch (1.2 mm) insulation maximum

Wire Category

2

1 - on signal ports

Terminal Base Screw Torque

0.6 Nm (7 lb-in)

Weight

0.036 kg (0.08 lb)