Rockwell Automation 1791-I0VW USER MANUAL User Manual

Page 10

Advertising
background image

Introducing Block I/O

Chapter 1

1-5

Figure 1.4

Sourcing Input Example

Field

Device

Input

+V

10917ĆI

Block I/O

dc Power

Supply

dc Common Bus

ĆV

In sinking outputs (Figure 1.5), the current flow is reversed. The dc
common is bussed on the module and the current is sourced from the field
device being actuated. When an output is turned on, the output switch in
the module sinks the circuit, causing current to flow from the +V bus
through the field device to the module.

Figure 1.5

Sinking Output Example

dc Power

Supply

Field

Device

Field

Device

+V

ĆV

Bus

Common

Fuse

Fuse

10918ĆI

Block I/O

Block I/O functions exactly like any Allen-Bradley remote I/O product.
Input and output data is scanned asynchronously and transferred back and
forth between the block and the controller input and output image table.

You connect the block I/O to your remote I/O link as you would any other
device. The block looks like a 1/4 I/O rack to the processor, and uses 2
words of input image table memory and 2 words of output image table
memory. The block is addressed directly on the remote I/O link.

Advertising
This manual is related to the following products: