3 - configuring your block i/o, Chapter objectives, Setting the configuration switches – Rockwell Automation 1791-I0VW USER MANUAL User Manual

Page 23: Configuring your block i/o

Advertising
background image

Chapter

3

3-1

Configuring Your Block I/O

In this chapter you will learn how to configure your block I/O when used
with PLC family programmable controllers. This includes the following:

setting the configuration switches

addressing the block I/O

To configure your block I/O for SLC family processors, refer to the user
manual for the 1747-SN scanner module.

ATTENTION: This module is not compatible with the
1747-DSN distributed I/O scanner module.

Each block I/O module has switches for setting:

transmission (baud) rate - used to set the communication rate chosen

for the remote I/O link

last state - when last state is enabled, a processor reset will keep the

outputs in their present (last) state; when last state is disabled, the
outputs will reset

processor restart lockout (PRL) - when PRL is enabled, the

programmable controller cannot automatically start up the module’s
communications if the power has been cycled to either the module or
the programmable controller

last rack - used to identify if the module contains the highest numbered

I/O group for the associated rack number

I/O group adress - used to identify which module group (0-1, 2-3, 4-5

or 6-7) the module should assign to its inputs/outputs

rack address - used to select the rack address of the module

RIO termination resistor - used to connect an internal resistor

(82 ohm, 150 ohm, or no resistor) across LINE 1 and 2 on the remote
I/O terminals

These switches are all accessible on the front or top of the module, as
shown in Figure 3.1.

Chapter Objectives

Setting the Configuration

Switches