Troubleshooting

Chapter 4

4-3

Table 4.A

Troubleshooting Chart

Indication

Probable Cause

Corrective Action

POWER

(

)

Green

I/O status on/off

Normal indication

None required

(green)

Off

No 24V dc power connected, or hardware fault.

Check 24V dc power to block

Solid green

Normal indication Ć module is communicating with

the programmable controller

None required

COMM

(green)

Off

No communication with adapter, scanner etc.

Check that power LED is on. Make sure that

proper number of blocks are configured.

(green)

Flashing green

Reset command (or output disable bit for SLC) has

been issued by processor, scanner or adapter.

SLC or programmable controller not in run mode.

Check program. Correct as necessary.

Place in run mode.

ACTIVE

Green

Normal indication

None

ACTIVE

(green/red) Red

Internal CPU fault

Return module for repair

FUSE

Red

One or more fuses are open

Replace blown fuse

FUSE

(red)

Off

Normal indication

None required

The block I/O module has one fuse for each group of outputs. To replace a
fuse, proceed as follows.

1.

Remove power to the block I/O module.

ATTENTION: Remove power to the block I/O module before
attempting to replace the fuse.

Failure to remove power from the block I/O module could

cause injury or equipement damage due to possible
unexpected operation.

Failure to remove power from the module could cause

module damage, degradation of performance or injury.

2.

Remove the four screws securing the cover to the block I/O module.

3.

Locate and remove the blown fuse.

Replacing a Fuse