A - specifications, Specifications – Rockwell Automation 1791-I0VW USER MANUAL User Manual

Page 37

Advertising
background image

Appendix

A

A-1

Specifications

General Specifications

External power

Range: 18 to 26.4V dc

100mA @ 24V dc; initial surge 2.0A for 10ms

Power Dissipation

15.1 Watts (maximum); 7.6 Watts (typical)

Thermal Dissipation

51.8 BTU/hr (maximum); 25.9 BTU/hr (typical)

Remote I/O Isolation

850V dc (transformer) for 1 second

Interconnect cable length

(PLC or SLC)

RIO:

57.6K

10,000 cable-feet

115.2K

5,000 cable-feet

230.4K

2,500 cable-feet

Cable requirements

RIO - Belden 9463

Dimensions

Inches:

6.15W x 7.0H x 1.75D

Millimeters: 156.21W x 178.0H x 44.7D

Conductors Wire Size

Category

14 gauge (2mm

2

) stranded (maximum)

3/64 inch (1.2mm) insulation (maximum)

2

1

Environmental Conditions

Operating Temperature

Storage Temperature

Relative Humidity

Operating

NonĆoperating

32 to 140

o

F (0 to 60

o

C)

-40 to 185

o

F (-40 to 85

o

C)

5 to 95% noncondensing

5 to 80% noncondensing

1

Refer to publication 1770-4.1, Programmable Controller Wiring and Grounding Guidelines

Input Specifications

Number of Inputs

32 (2 groups of 16)

Input type

1791-IOBW - Sinking; 1791-IOVW - Sourcing

On-state voltage range

12.0 to 26.4V dc

Minimum on-state input current

1.56mA

Maximum off-state voltage

7.0V dc

Maximum off-state current

1.0mA dc

OnĆstate Current (typical)

5.2mA @ 24V dc

Input Impedance (nominal)

4.6K

Maximum turn on time

10msec (+4ms)

Maximum turn off time

10msec (+4ms)

Input to system isolation

1500V ac (opto) for 1 second

Group to group isolation

1500V ac (air gap) for 1 second

Advertising