Status Indicators - Bi-color LED indicators provide power, active,
communication and fuse blown indications. An LED array provides
input/output status.

Indicator

Indication

Power (green/wht)

On (green)

Customer voltage is present

Power (green/wht)

Off (wht)

No customer voltage

Active (green/red)

On (green)

CPU operating correctly

Active (green/red)

Off (red)

CPU not running

Comm (green/wht)

On (green)

Communication correctly established

Comm (green/wht)

Off (wht)

Communication not established

Fuse (red/wht)

On (red)

One of the fuses is open

Fuse (red/wht)

Off (wht)

Both fuses are intact

The I/O status array is an 8 by 8 array of 64 LEDs capable of displaying
the status of 32 inputs and 32 outputs at any one time.

Block I/O is a complete I/O interface that includes the functionality of the
I/O rack, adapter, power supply, and I/O modules in a single unit. Simply
connect sensors and actuators to the module and use the remote I/O cable
to connect the block I/O to your programmable controller (Figure 1.6).

The 1791-IOBW block uses sinking inputs and sourcing outputs.

In sinking inputs, the dc common is bussed on the block. and the current is
sourced from the field device. The sourcing field device switches the hot
side of the power supply bus causing current to flow through the sourcing
device to the sinking input on the block. Refer to Figure 1.2.