background image

dc (10…60V) Output Module 15

Publication 1771-IN054C-EN-P - November 2006

Specifications

dc (10…60V) Output Module, 1771-OBD Series C

Attribute

Value

Outputs per module

16 nonisolated

Module location

1771-A1B through 1771-A4B I/O chassis (Do not use this module
with 1771-A4 I/O chassis)

User supply voltage

10…60V dc

Voltage, on-state output, nom

48V dc

Current rating (see Derating Curve)

2 A per output resistive, not to exceed 8 A per module

0.2 A per output pilot duty

Surge current, max

4 A per output for 10 ms, repeatable every 2 s

25 A per output for 10 ms, repeatable every 2 s

Load current, min

2.5 mA

On-state voltage drop (at rated
current), max

1.5V dc

Off-state leakage current, max

0.5 mA

Output signal delay, max

Off to on

On to off


0.1 ms

0.2 ms

Power dissipation, max

15.6 W

Thermal dissipation, max

53.3 BTU/hr

Isolation voltage (continuous-voltage
withstand rating)

60V (continuous), Basic Insulation Type

Tested at 1000V ac for 60 s, I/O to system

Backplane current, max

400 mA @ 5V dc

Conductors wire size


Category

(1)

(1)

Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and

Grounding Guidelines, publication 1770-4.1.

0.34…2.5 mm

2

(22…14 AWG) solid or stranded copper wire rated

at 120 °C (248 °F) or higher

1.2 mm (3/64 in.) insulation max

2 - on signal ports

Temperature code, IEC

T3

Temperature code, North America

T3C

Field wiring arm

1771-WH

1771-WHF (3 A fused)

(2)

1771-WHFB (1.5 A fused)

(2)

(2)

Not suitable for Class I Division 2 Groups A, B, C, and D Hazardous Locations.

Field wiring arm screw torque

1.0 Nm (9 lb-in)

Keying

Between 10 and 12

Between 22 and 24