Rockwell Automation 1771-OBD Series C INSTL INSTR DC(10-60V) OUTPUT User Manual

Page 16

Advertising
background image

16 dc (10…60V) Output Module

Publication 1771-IN054C-EN-P - November 2006

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60 °C (32…140 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
–40…85 °C (–40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):

2 g @ 10…500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):

50 g

ESD immunity

IEC 61000-4-2:

4 kV indirect contact discharges

Radiated RF immunity

IEC 61000-4-3:

10 V/m with 1 kHz sine-wave 80% AM from 30…1000 MHz

EFT/B immunity

IEC 61000-4-4:

±1 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…30 MHz

Emissions

CISPR 11:

Group 1, Class A (with appropriate enclosure)

Enclosure type rating

None (open style)