Step 1 - Preparing the PLC-5 Processor

1. Save processor memory to your hard disk or to an EEPROM using your

PLC-5 programming software.

2. Remove the processor battery cover and disconnect the battery. This resets

the serial port to its default configuration so that the PLC-5 processor and the
flash tool can communicate.

3. Turn off processor power.

4. Disconnect all cables (serial, DH+

, ControlNet, Ethernet, etc.) from

the processor.

5. Disconnect the coprocessor or PLC-5 Ethernet Interface module, if one

is connected.

6. Turn the processor keyswitch to Program mode.

7. Turn on processor power.

8. Attach the shielded serial cable (1784-CP10 or 1784-CP11) between

channel 0 on the PLC-5 processor and the serial port on the computer.

!

ATTENTION: You must save the processor memory
to your hard disk or to an EEPROM. If you do not, the
PLC-5 user memory will be lost because the flash
procedure erases processor memory.