For a-b internal use only – Rockwell Automation 1785 User Mnl. PLC-5 Prog.Control Flash User Manual

Page 5

Advertising
background image

5

For A-B Internal Use Only

Publication 1785-6.2 March 1998

3. Select the appropriate script file by moving the cursor to the file name and

pressing

. Script files are named as follows:

Lwwx_yz.ini

4. On your computer, select the communication port (COM1 or COM2) by

moving the cursor to select the port and pressing

.

5. Make sure you have established a connection. This could take about

60 seconds.

Where:

Represents:

ww

11, 20, 26, 30, 40, 46, 60, 80, or 86

depending on what flash upgrade you are
trying to download to the processor.

x

the type of flash upgrade to download:
• B (for Enhanced)
• L (for Extended-local I/O)
• C (for ControlNet 1.0 or 1.25)
• E (for Ethernet)
• C15 (for ControlNet 1.5)

y

the series of the flash upgrade to download
(see the disk label)

z

the revision of the flash upgrade to download
(see the disk label)

If you:

The screen displays:

established a connection

information about the target processor

The processor’s PROC LED flashes
red/green.

did not establish a connection

an error message

See the following table.