If you received an error:

When the flash download begins:

the processor’s COMM LED blinks green

the processor’s PROC LED blinks red/green

a percent complete status (0 - 100) appears in the middle
of the screen that indicates how much of the flash update
is complete

6. Wait for the flash update to complete. The upgrade should take

about 5 minutes to complete.

When the download is complete the status bar will be at 100%
and the screen will display this message:

Processors Flash

Update Completed. Press Any Key to Continue.

If you received this error:

Do this:

Processor not connected.

a. Make sure the keyswitch is in Program

mode.

b. Make sure the processor power is on.

c. Check the serial cable.

d. Verify the COM port being used by the

computer.

e. Return to item 3, step 3 on page 5 and

repeat this section.

Target processor does

not match script file.

a. Check the name of the script file.

b. Make sure you are connected to the correct

type and series of processor.

c. Return to item 3, step 3 on page 5 and

repeat this section.

Firmware series stated

in script file does not

match PLC.

a. Make sure you are connected to the correct

type and series of processor.

b. Return to item 3, step 3 on page 5 and

repeat this section.

No script files found.

a. Make sure you copied all files from the

firmware upgrade diskette to the c:\flash
hard drive directory as described in item 2,
step 2 on page 4.

b. Make sure you selected the catalog number

of the flash upgrade you want to
download to the processor on the flash
upgrade catalog number selection
screen. Do not select the catalog number
of the processor you currently have.

c. Return to item 3, step 3 on page 5 and

repeat this section.