System wiring guidelines – Rockwell Automation 1769-IF16C Conpact High Density Analog Current Input Module User Manual

Page 12

Advertising
background image

12 Compact High-density Analog Current Input Module

Publication 1769-IN085A-EN-P - August 2008

System Wiring Guidelines

Consider the following when wiring your system:

All module commons (COM) are connected in the analog module.

The analog common (COM) is not connected to earth ground inside the
module.

Channels are not isolated from each other.

Use Belden 8761, or equivalent, shielded wire.

Under normal conditions, the drain wire and shield junction must be
connected to earth ground via a panel or DIN rail mounting screw at the
analog I/O module end. Keep the shield connection to ground as short as

possible.

(1)

To ensure optimum accuracy, limit overall cable impedance by keeping your
cable as short as possible. Locate the I/O system as close to your sensors or

actuators as your application will permit.

(2)

If multiple power supplies are used with analog inputs, the power supply
commons must be connected.

The 1769-IF16C module does not provide loop power for analog inputs. Use
a Class 2-rated power supply that matches the input transmitter
specifications.

Voltages on the IN+ terminals of the 1769-IF16C module must be within
+/-10V DC of analog common.

(1)

In environments where high-frequency noise may be present, it may be necessary to directly ground cable shields to earth
at the module end and via a 0.1 µF capacitor at the sensor end.

(2)

Cable length over 50 m (164 ft) may impact accuracy. For details, refer to the Compact High-Density Analog Input Modules
User Manual, publication

1769-UM018.

ATTENTION

Be careful when stripping wires. Wire fragments that fall into a
module could cause damage at power up. Once wiring is complete,
ensure the module is free of all metal fragments.

Advertising