Remove the finger-safe terminal block – Rockwell Automation 1769-IF16C Conpact High Density Analog Current Input Module User Manual
Page 13

Compact High-density Analog Current Input Module 13
Publication 1769-IN085A-EN-P - August 2008
Wire Input Sensors/Transmitters
Label the Terminals
A removable, write-on label is provided with the module. Remove the label from
the door, mark the identification of each terminal with permanent ink, and slide the
label back into the door. Your markings (ID tag) will be visible when the module
door is closed.
Remove the Finger-safe Terminal Block
When wiring field devices to the module, it is not necessary to remove the terminal
block. If you remove the terminal block, use the write-on label on the side of the
terminal block to identify the module slot location and type.
To remove the terminal block, loosen the upper and lower retaining screws. The
terminal block will back away from the module as you remove the screws. When
replacing the terminal block, torque the retaining screws to 0.46 N
•
m (4.1 in
•
lbs).
+
IN1+
IN0+
IN3+
IN2+
IN5+
IN4+
IN7+
IN8+
IN6+
IN9+
IN11+
IN10+
IN12+
IN13+
IN15+
IN14+
Com
Com
+
+
-
Current
Transmitter
Sensor/
Transmitter
Power
Supply
(1)
Current Transmitter
Signal
Signal
Ground
1769-IF16C Terminal Block
(1) The sensor power supply must be rated Class 2.
SLOT # ____
MODULE TYPE _____
R
L
RoHS