Compact High-density Analog Current Input Module 15
Publication 1769-IN085A-EN-P - August 2008
Configure the 1769-IF16C Module
Use the following I/O memory mapping tables to configure the 1769-IF16C module.
Output Data File
For each module, slot x, words 0 and 1 in the output data file contain the cancel
latched channel alarm control bits.
The bits are defined as follows:
•
CLH
x = Cancel High Process Alarm Latch for Input x: Allows each input
high-process-alarm latch to be individually cancelled. Cancel = 1.
•
CLL
x = Cancel Low Process Alarm Latch for Input x: Allows each input
low-process-alarm latch to be individually cancelled. Cancel = 1.
Word/
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Word 0 CL
L7
CL
H7
CL
L6
CL
H6
CL
L5
CL
H5
CL
L4
CL
H4
CL
L3
CL
H3
CL
L2
CL
H2
CL
L1
CL
H1
CL
L0
CL
H0
Word 1 CL
L15
CL
H15
CL
L14
CL
H14
CL
L13
CL
H13
CL
L12
CL
H12
CL
L11
CL
H11
CL
L10
CL
H10
CL
L9
CL
H9
CL
L8
CL
H8