Rockwell Automation 1769-IF16C Conpact High Density Analog Current Input Module User Manual
Page 22

22 Compact High-density Analog Current Input Module
Publication 1769-IN085A-EN-P - August 2008
Bit Definitions for Channel Configuration Words
Define
To Choose
Make these bit settings
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Input Filter
Selection
60 Hz
0
0
0
0
50 Hz
0
0
0
1
16 Hz
0
0
1
0
315 Hz
0
0
1
1
1365 Hz
0
1
0
0
Enable
Interrupt
(1)
(1)
Alarm interrupts are not supported by all bus masters. Check your controller’s user manual to determine if expansion I/O
interrupts are supported.
Enable
1
Disable
0
Process
Alarm
Latch
Enable
1
Disable
0
Enable
Process
Alarms
Enable
1
Disable
0
Enable
Channel
Enable
1
Disable
0
Bit Definitions for Input Range and Input Data Configuration
Define
To Choose
Make these bit settings
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Input
Range
Select
4…20 mA
0
0
0
0
0…20 mA
0
0
0
1
Input
Data
Format
Select
Proportional
Counts
0
0
0
Engineering
Units
0
0
1
Scaled for PID
0
1
0
Percent
Range
0
1
1