22 Compact High-density Analog Current Input Module

Publication 1769-IN085A-EN-P - August 2008

Bit Definitions for Channel Configuration Words

Define

To Choose

Make these bit settings

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Input Filter
Selection

60 Hz

0

0

0

0

50 Hz

0

0

0

1

16 Hz

0

0

1

0

315 Hz

0

0

1

1

1365 Hz

0

1

0

0

Enable

Interrupt

(1)

(1)

Alarm interrupts are not supported by all bus masters. Check your controller’s user manual to determine if expansion I/O
interrupts are supported.

Enable

1

Disable

0

Process
Alarm
Latch

Enable

1

Disable

0

Enable
Process
Alarms

Enable

1

Disable

0

Enable
Channel

Enable

1

Disable

0

Bit Definitions for Input Range and Input Data Configuration

Define

To Choose

Make these bit settings

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Input
Range
Select

4…20 mA

0

0

0

0

0…20 mA

0

0

0

1

Input
Data
Format
Select

Proportional
Counts

0

0

0

Engineering
Units

0

0

1

Scaled for PID

0

1

0

Percent
Range

0

1

1