10 ArmorBlock MaXum 4 Input / 4 Output Module Series B

Publication 1792D-IN012B-EN-P - September 2000

Troubleshoot with the Indicators

This module has the following indicators:

• Network/Module status indicator
• Logic status indicators
• Auxiliary Power indicator
• Individual point status indicators for inputs

The following table describes the network and module status

indicator.

Net/Mod Status Indicator

Indication

Status:

Off

No power or auto bauding

Flashing Green/Off

On line but not connected

Solid Green

On line, link OK, connected

Flashing Red

Recoverable fault - module configuration error

I/O connection fault - one or more I/O connections in the timed-out
state

Solid Red

Unrecoverable fault

Communication failure - duplicate node address present or incorrect
baud rate

Green to Red to Off At powerup only - LED test

I0

I1

I2

I3

O0

O1

O2

O3

Auxiliary Power

Logic Status

Net/Mod Status

Point indicators
for inputs 0 and 1

30706-M

Point indicators for
outputs 0 and 1

Module Status Indicators

Point indicators
for inputs 2 and 3

Connector A

Connector B

Point indicators
for outputs 2 and 3

Connector C

Connector D

LED Assignments