ArmorBlock MaXum 4 Input / 4 Output Module Series B 9

Publication 1792D-IN012B-EN-P - September 2000

The DeviceNet Network uses advanced network technology,
producer/consumer communication, to increase network
functionality and throughput. Visit our web site at http://
www.ab.com/networks for producer/consumer technology
information and updates.

Byte

Bit

Description

Produces 0

00-03

04

05

06-07

Input status bits: When the bit is set (1), the input is on. Bit
00 corresponds to input 0, bit 01 corresponds to input 1, bit
02 corresponds to input 2, bit 03 corresponds to input 3.
Input short circuit fault (ISC): ISC-A indicates a short circuit
for connector A.
Input short circuit fault (ISC): ISC-B indicates a short circuit
for connector B.
Input off wire fault (OW): OW-A indicates an off-wire fault
for connector A. OW-B Indicates an off-wire fault for
connector B.

Produces 1

00-03

04-05
06

07

Output no load or overload fault (OFLT): - When the bit is set
(1) an output fault has occurred. OFLT0 corresponds to output
0, OFLT1 corresponds to output 1, OFLT2 corresponds to
output 2, OFLT3 corresponds to output 3.
Reserved
Output Power Fault (OPWR): When the bit is set (1) Auxiliary
Power is not present.
Reserved

Consumes 0

00-03

04-07

Output bits: When the bit is set (1), the output will be turned
on. Bit 00 corresponds to output 0, bit 01 corresponds to
output 1, bit 02 to output 2, bit 03 to output 3.
Reserved

Advertising