14 CompactBlock Guard I/O DeviceNet Safety Modules

Publication

1791DS-IN002C-EN-P - April 2009

Flashing
red

One or more I/O
connections in
timed-out state or
user-initiated firmware
update in progress

The module detected a recoverable network fault
or user-initiated firmware update is in progress.

Solid red

Critical link failure

The module detected an error that prevents it from
communicating on the network.

Flashing
red and
green

Communication faulted
module

The module detected a network access error and is
in communication faulted state. The module
received and accepted an Identity Communication
Faulted Request-long protocol message.

(1)

For recommended action, refer to the user manual that covers these modules.

Safety Input Status Indicator

State

Status

Description

Recommended Action

Off

Safety input
off or module
being
configured

The safety input is off or the
module is being configured.

Turn the safety input on or
wait for the module to be
configured.

Solid
yellow

Safety input
on

The safety input is on.

None.

Solid red

Fault detected

A fault in the external wiring
or input circuit detected.

Check configuration, field
wiring, and devices. If no
problem found, replace
module.

Flashing
red

Partner fault
detected

A fault in the partner input
circuit of a dual input
configuration detected.

Check the field wiring and
verify your configuration for
the partner circuit. If no
problem found, replace
module.

Network Status Indicator

(1)

State

Status

Description