CompactBlock Guard I/O DeviceNet Safety Modules 9

Publication

1791DS-IN002C-EN-P - April 2009

Wiring the Module

Follow these guidelines when wiring the module:

Do not route communication, input, or output wiring with conduit

containing high voltage, referring to Industrial Automation Wiring
and Grounding Guidelines, publication

1770-4.1

.

• Wire correctly after confirming the signal names of all terminals.
• Note that stranded wire should be processed with insulation-covered

ferrule (DIN 46228-4 standard compatible-type) at its ends before
using for connection.

• Tighten screws for communication and I/O connectors correctly at

0.25…0.3 N•m (2.21…2.66 lb•in).

Working with Connectors

See the figure that shows connectors.

Power and DeviceNet Connectors

DeviceNet Configuration

Color

Signal

Red

V+

White

CAN_H

-

Drain

Blue

CAN-L

Black

V-

Power Configuration

Pin

Signal

1

Input +24V DC Power

2

Input Power Common

3

Output +24V DC Power

(1)

(1)

NC on 1791DS-IB16 modules.

4

Output Power Common

(1)

44045

44046

1

2

3

4

Red

White

-

Blue
Black