8 CompactBlock Guard I/O DeviceNet Safety Modules

Publication

1791DS-IN002C-EN-P - April 2009

Mount the Module

Use these procedures when mounting the module:

• Use horizontal or vertical mounting with a DIN rail that is 35 mm

(1.4 in.) wide for placing the module in the control panel.

• Leave at least 15 mm (0.6 in.) above and below the module for

adequate ventilation and room for wiring.

• Place all other heat sources an appropriate distance from the module

to maintain the specified ambient temperature around the module.

Module Identification and Dimensions

See the figure for module identification and dimensions.

75.91 mm (2.99 in.)

60.41 mm

(2.38 in.)

81.0

17 m

m

(3

.19 i

n.)

65.5

mm

(2.58

in.)

170 mm (6.7 in.)

Node Address Switch

Communication Connector

I/O Connectors (input)

44071

I/O Connectors
(output)

Power
Connector

1791DS-IB8XOBV4 module is shown.
1791DS-IB16 module dimensions are identical.