Rockwell Automation 1791DS-IB16 CompactBlock Guard I/O DeviceNet Safety Module  User Manual

Page 22

Advertising
background image

22 CompactBlock Guard I/O DeviceNet Safety Modules

Publication

1791DS-IN002C-EN-P - April 2009

EFT/B immunity

IEC 61000-4-4:
±2 kV at 5 kHz on power ports
±2 kV at 5 kHz on signal ports
±2 kV at 5 kHz on communication ports

Surge transient
immunity

IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM)
on power ports
±1 kV line-line (DM) and ±2 kV line-earth (CM)
on signal ports
±2 kV line-earth (CM) on communication ports

Reaction Time

Input reaction time,
max

16.2 ms + set values of ON/OFF delays

Output reaction time,
max

6.2 ms + (20 ms) relay response time (1791DS-IB8XOBV4 module
only)

Typical Signal Sequence

Environmental Specifications

Attribute

Value

Typ. 600 ms

44072

While safety outputs are in an on state, the signal sequence shown in the figure is
output continuously for fault diagnosis when output pulse testing is enabled.
Confirm response time of device connected to safety outputs so the device does not
malfunction due to off pulse.

Typ. 700

μs

Advertising
This manual is related to the following products: