DeviceNet Daughtercard 11

Publication 1788-IN053A-EN-P - December 2001

Module Command Register Bit Definitions

The bits of the Module Command Register are defined as follows:

Input Structure

The controller receives input I/O by reading input data from an input structure in the
1788-DNBO daughtercard. The daughtercard receives input data from DeviceNet modules
and delivers a copy of these values to the controller. The input structure consists of one 32-bit
status register and a variable size 32-bit array of up to 124 words for input data. The 32-bit
status register reflects the current state of several key module-level operational parameters.
The input structure consists of these data elements.

Bit

Name

Description

0

Run

1 = run mode

0 = idle mode

1

Fault

1 = fault network

2

DisableNetwork

1 = disable network

3

HaltScanner

1 = halt module
(The daughtercard ceases all operation.)

4

Reset

1 = reset module

(Put back to 0 to resume operation.)

5 - 31

{Reserved}

unused

IMPORTANT

If the daughtercard is halted because the HaltScanner
bit is set, power must be physically recycled to restart
the module.

Input Structure Element

Data Type

module status register

1 x 32-bit register

input_data

123 x 32-bit variable size
data array