Specifications – Rockwell Automation 1788-DNBO DeviceNet Daughtercard Installation Instructions User Manual

Page 15

Advertising
background image

DeviceNet Daughtercard 15

Publication 1788-IN053A-EN-P - December 2001

Specifications

Characteristic

Value

Power Requirements

Host

DeviceNet

5V dc @ 260mA

(1)

24V dc @ 20mA Class 2

Power Consumption

Thermal Dissipation

5 V dc, 1.3W
24 V dc, 0.48W.
Total=1.78W
6.1 BTU/hr

Isolation Voltage

Tested to withstand 707 V dc for 60 seconds

RTB Screw Torque

5-7 inch-pounds (0.56-0.8 Nm)

Conductors Wire Size

Category

24-12 AWG (0.205-3.31 mm

2

) stranded copper

(2)

3/64 inch (1.2mm) insulation maximum
2

(2)

Emissions

CISPR 11: Group 1, Class A (with appropriate enclosure)

ESD Immunity

IEC 61000-4-2:
6kV contact discharges
8kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz

EFT/B Immunity

IEC 61000-4-4:
±2kV at 5kHz on communications ports

Surge Transient Immunity

IEC 61000-4-5:
+2kV line-earth (CM) on shielded ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Enclosure Type Rating

None (open-style)

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
This product is suitable for application in equipment that is rated 0 to 60

o

C

(32 to 140

o

F) maximum. It is acceptable for the ambient slot temperature

immediately surrounding this

product to reach 85

o

C (185

o

F) maximum.

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Un-packaged Non-operating Thermal Shock):
–40 to 85°C (–40 to 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):
5 to 95% non-condensing

Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g
Non-operating 50g