Specifying the serial interface of channel 0 – Rockwell Automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controllers User Manual User Manual
Page 24

1785-UM022C-EN-P - February 2008
1-12
Installing Your ControlNet PLC-5 Processor
Specifying the Serial
Interface of Channel 0
Specify RS-232C, RS-422A, or RS-423 communication for Channel
0 by setting the switches of assembly SW2.
Selecting the ControlNet
Network Address of
Channel 2
Select your processor’s ControlNet network address by setting the
two 10-digit rotary switches on the top of the processor.
You can select from as many as 99 network addresses (from 01 to 99)
for a processor on a ControlNet link. 0 is invalid.
Important: Do not power-up the processor if the processor’s
ControlNet network address is set to 0. If you do, you
will not be able to communicate with your processor and
your ladder program will be lost, even if you have a
battery installed. If this happens, select a valid network
address for the processor and cycle power.
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
Front of processor
Front of processor
Bottom View of PLC-5/20C Processor
Switch Assembly SW2
Bottom View of PLC-5/40C, -5/46C, -5/80C Processor
Switch Assembly SW2
To Specify:
Set Switches:
1
2
3
4
5
6
7
8
9
10
RS-232C
RS-422A
RS-423
Toggle pushed
ON
Toggle pushed
OFF
toward BOTTOM
toward TOP
ON
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
00
10
20
30
40
50
60
70
80
90
0
1
2
3
4
5
6
7
8
9
NET ADDRESS
Network address 01
is shown
For optimum throughput, assign addresses
to your ControlNet nodes in a sequential
order starting with 01.