Specifying the serial interface of channel 0 – Rockwell Automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controllers User Manual User Manual

Page 24

Advertising
background image

1785-UM022C-EN-P - February 2008

1-12

Installing Your ControlNet PLC-5 Processor

Specifying the Serial

Interface of Channel 0

Specify RS-232C, RS-422A, or RS-423 communication for Channel
0 by setting the switches of assembly SW2.

Selecting the ControlNet

Network Address of

Channel 2

Select your processor’s ControlNet network address by setting the
two 10-digit rotary switches on the top of the processor.

You can select from as many as 99 network addresses (from 01 to 99)
for a processor on a ControlNet link. 0 is invalid.

Important: Do not power-up the processor if the processor’s

ControlNet network address is set to 0. If you do, you
will not be able to communicate with your processor and
your ladder program will be lost, even if you have a
battery installed. If this happens, select a valid network
address for the processor and cycle power.

1

2

3

4

5

6

7

8

9

10

1

2

3

4

5

6

7

8

9

10

Front of processor

Front of processor

Bottom View of PLC-5/20C Processor
Switch Assembly SW2

Bottom View of PLC-5/40C, -5/46C, -5/80C Processor
Switch Assembly SW2

To Specify:

Set Switches:

1

2

3

4

5

6

7

8

9

10

RS-232C

RS-422A

RS-423

Toggle pushed

ON

Toggle pushed

OFF

toward BOTTOM

toward TOP

ON

ON

ON

OFF

OFF

ON

ON

OFF

ON

OFF

OFF

OFF

ON

OFF

OFF

OFF

OFF

OFF

ON

OFF

ON

ON

ON

OFF

OFF

ON

OFF

OFF

ON

OFF

00

10

20

30

40

50

60

70

80

90

0

1

2

3

4

5

6

7

8

9

NET ADDRESS

Network address 01
is shown

For optimum throughput, assign addresses
to your ControlNet nodes in a sequential
order starting with 01.

Advertising