Rockwell Automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controllers User Manual User Manual
Page 64

1785-UM022C-EN-P - February 2008
2-26
Planning to Use Your ControlNet PLC-5 Processor
Second Rule of
Module Optimization
Place modules that do not require I/O image table space to the right
in the chassis.
Example 4
To understand how optimization with a ControlNet network preserves
I/O image space, look at the following example system:
The following chart shows how a Remote I/O system compares to
one optimized with a ControlNet network.
If you install the system on a PLC-5/20C processor, the Remote I/O
network option would be out of I/O image space, while the
ControlNet network option would have used only one-third of the
available I/O image space. You must take into account future
expansion when optimizing the I/O.
I = Discrete Input Module
O = Discrete Output Module
ACN = ControlNet adapter
A = Analog Module
PS = Power Supply
Chassis 1
Chassis 2
Chassis 3
ACN
A
A
A
A
A
a
A
PS
A
A
ACN
I
O
O
O
O
O
O
PS
ACN
O
I
I
I
I
I
I
PS
Remote I/O
ControlNet Network
Input
Output
Input
Output
Chassis
Address
Size
Address
Size
Address
Size
Address
Size
1
2
3
I:010
I:020
I:030
8
8
8
O:010
O:010
O:030
8
8
8
I:010
I:011
n/a
1
7
0
O:010
O:017
n/a
7
1
0
Total Used
24 (3 racks)
24 (3 racks)
8 (1 rack)
8
Remaining
0
0
16 (2 racks)
16