Installing Your ControlNet PLC-5 Processor
1-23
This processor’s serial port can support these configurations:
Important: Follow these guidelines:
•
When Channel 0 is configured for RS-422A compatibility, do not
use terminating resistors anywhere on the link.
•
When Channel 0 is configured for RS-422A (compatible) and
RS-423, do not go beyond 61 m (approximately 200 ft). This
distance restriction is independent of the transmission rate.
DH+ Programming Cables
Remote I/O Cables
Use 1770-CD or cable for remote I/O. See Inserting/Removing the
Processor into/from the I/O Chassis on page 1-13 for more
information.
ControlNet Cables
Several types of RG-6 quad-shield cable may be appropriate for your
ControlNet installation—depending on the environmental factors
associated with your application and installation site.
Digital Interface
Maximum Cable Length
RS-232C
15 m (approximately 50 ft)
RS-422A (compatible)
61 m (approximately 200 ft)
RS-423
61 m (approximately 200 ft)
When using this
communication card:
Use this cable:
1784-KTX, KTXD
• 1784-CP13
1784-PCMK
• 1784-PCM6
• 1784-PCM5 with 1784-CP7 adapter
1784-PKTX, -PKTXD
• 1784-CP13