Rockwell Automation 1785-Lx0C15 ControlNet PLC-5 Programmable Controllers User Manual User Manual
Page 51

1785-UM022C-EN-P - February 2008
Planning to Use Your ControlNet PLC-5 Processor
2-13
If an input only connection is made to the adapter:
•
an exclusive owner connection can be made
•
another input only connection can be made
•
a listen only connection can be made
•
a redundant owner connection can be made
A listen only connection can only be made to the adapter if:
•
an exclusive owner connection already exists, or
•
an input only connection already exists, or
•
a redundant owner connection already exists
If a redundant owner connection is made to the adapter:
•
an exclusive owner connection will be rejected
•
an input only connection can be made
•
a listen only connection can be made
•
another identical redundant owner connection can be made
Multiple Processors Can Control I/O on the Same ControlNet
Link
A processor at any valid node address can control the outputs of a
particular module or rack. However, only one processor can control
the same outputs at any one time.
In the following figure, the processor at node 1 can control the
outputs of node 2 while the processor at node 3 controls the outputs of
node 4.
node 1
node 2
node 3
node 4