16 ControlLogix SERCOS interface Module
Publication
1756-IN572G-EN-P - May 2005
Number of Drives
1756-M03SE
Up To 3 SERCOS interface drives
1756-M08SE
Up to 8 SERCOS interface drives
1756-M16SE
Up to 16 SERCOS interface drives
1756-M08SEG
Up to 8 SERCOS interface drives. You
must use drives that are Extended Pack
Profile compliant.
SERCOS interface
Data Rate
1756-M03SE
4 Mbits or 8 Mbits per second
1756-M08SE
4 Mbits or 8 Mbits per second
1756-M16SE
4 Mbits or 8 Mbits per second
1756-M08SEG
4 Mbits per second
SERCOS interface
Cycle Time
Important: Only Kinetix 6000 drives let you use a 0.5 ms cycle time.
Data rate
Number of drives
Cycle time
4 Mb
up to 2
0.5 ms
up to 4
1 ms
up to 8
2 ms
You can’t use more than 8 drives at a 4 Mb
data rate.
8 Mb
up to 4
0.5 ms
up to 8
1 ms
up to 16
2 ms
Plastic Fiber Optic
Cable
Transmission Range
1-32 meters
Core Diameter
980
μm ± 60μm
Cladding Diameter
1000
μm ± 60μm
Cable Attenuation
140 dB/km @ 650nm
Operating Temperature
-55 to 85
° C
Connector
F-SMA standard screw-type connector
Bend Radius
2.5 cm
Description