Rockwell Automation 1756-Mxxxx ControlLogix SERCOS interface Module Installation Instructions User Manual

Page 16

Advertising
background image

16 ControlLogix SERCOS interface Module

Publication

1756-IN572G-EN-P - May 2005

Number of Drives

1756-M03SE

Up To 3 SERCOS interface drives

1756-M08SE

Up to 8 SERCOS interface drives

1756-M16SE

Up to 16 SERCOS interface drives

1756-M08SEG

Up to 8 SERCOS interface drives. You
must use drives that are Extended Pack
Profile compliant.

SERCOS interface
Data Rate

1756-M03SE

4 Mbits or 8 Mbits per second

1756-M08SE

4 Mbits or 8 Mbits per second

1756-M16SE

4 Mbits or 8 Mbits per second

1756-M08SEG

4 Mbits per second

SERCOS interface
Cycle Time

Important: Only Kinetix 6000 drives let you use a 0.5 ms cycle time.

Data rate

Number of drives

Cycle time

4 Mb

up to 2

0.5 ms

up to 4

1 ms

up to 8

2 ms

You can’t use more than 8 drives at a 4 Mb
data rate.

8 Mb

up to 4

0.5 ms

up to 8

1 ms

up to 16

2 ms

Plastic Fiber Optic
Cable

Transmission Range

1-32 meters

Core Diameter

980

μm ± 60μm

Cladding Diameter

1000

μm ± 60μm

Cable Attenuation

140 dB/km @ 650nm

Operating Temperature

-55 to 85

° C

Connector

F-SMA standard screw-type connector

Bend Radius

2.5 cm

Description

Value

Advertising