ControlLogix SERCOS interface Module 9

Publication

1756-IN572G-EN-P - May 2005

Flashing
Red

The module has detected
a setup or configuration
fault with the ring.

Check your system setup and configuration as
follows:.

• Ensure drive and axes addresses are correct.
• Remove excess axes from ring.
• Make sure application program has selected

the proper Ring Cycle Period and Baud Rate.

Solid Red

The module has detected
a hardware or installation
fault with the ring.

Check your system hardware and installation as
follows:
• Make sure all cables are properly installed.
• Make sure cable is of the correct type and

length.

• Make sure application program has configured

the module’s ring transmit level to High when
using specified cables.

• Make sure the drive’s transmit levels are set

appropriately.

• Inspect cables for degradation.
• Inspect drives for any faults and correct them.

Off

The module has detected
no ring data on its
receiver or has not
successfully completed
phase 2.

Check your system and installation as follows:
• Make sure all cables are properly installed
• Inspect cable for degradation and breakage.
• Inspect drives for faults.

Flashing
Green

The ring, drive, or axes
are not configured but at
least one has been
identified.

Not a problem if the system has not been
configured. If you are having trouble configuring
the ring, drive, and axes, make sure that the
RSLogix 5000 project is setup properly for the
equipment in use.

Table 2 SERCOS Ring Status Indicator (Continued)

State

Description

Recommended Action