Basic input wiring to the 1762-if4 module – Rockwell Automation 1762-IF4 MicroLogix Analog Input Module User Manual

Page 13

Advertising
background image

MicroLogix 1762-IF4 Analog Input Module 13

Publication 1762-IN012C-EN-P - June 2013

Basic Input Wiring to the 1762-IF4 Module

Differential Sensor Transmitter Types

TIP

Grounding the cable shield at the module end only usually provides sufficient
noise immunity. However, for best cable shield performance, earth ground the
shield at both ends, using a 0.01µF capacitor at one end to block AC power
ground currents, if necessary.

IN 0 (+)

IN 0 (-)

IN 3 (+)

IN 3 (-)

IN 2 (+)

IN 2 (-)

COM

IN 1 (-)

IN 1 (+)

COM

Analog Sensor

Advertising