Labeling the Terminals

A write-on label is provided with the module. Mark the identification of each terminal with
permanent ink, and slide the label back into the door.

1762 Expansion I/O Addressing

The addressing scheme for 1762 Expansion I/O is represented in the following figure.

Input Data File

For each module, slot x, words 0…3 contain the analog values of the inputs. The module can be
configured to use either raw/proportional data or scaled-for-PID data. The input data file for
either configuration is shown below.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

SGN0

Channel 0 Data

1

SGN1

Channel 1 Data

2

SGN2

Channel 2 Data

3

SGN3

Channel 3 Data

4

reserved

S3

S2

S1

S0

5

U0

O0

U1

O1

U2

O2

U3

O3

reserved

6

reserved

I1:x.0/0

Slot number

(1)

Data file

Input

Slot delimiter

Word delimiter

Bit delimiter

Bit (0...15)

Word

(1)

I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins with slot 1.